Parameter
TRK_VAL
FF_VAL
FF_SCALE
FF_GAIN
UPDATE_EVT
BLOCK_ALM
ALARM_SUM
ACK_OPTION
ALARM_HYS
HI_HI_PRI
HI_HI_LIM
HI_PRI
HI_LIM
LO_PRI
LO_LIM
LO_LO_PRI
LO_LO_LIM
DV_HI_PRI
DV_HI_LIM
DV_LO_PRI
DV_LO_LIM
Rev.5
The value (after scaling from TRK_SCALE to OUT_SCALE)
APPLIED to OUT in LO mode.
The feedforward control input value and status.
The high and low scale values, engineering units code, and number
of digits to the right of the decimal point associated with the
feedforward value (FF_VAL).
The feedforward gain value. FF_VAL is multiplied by FF_GAIN
before it is added to the calculated control output.
This alert is generated by any changes to the static data.
The block alarm is used for all configuration, hardware, connection
failure, or system problems in the block. The cause of the alert is
entered in the subcode field. The first alert to become active sets the
active status in the status parameter. As soon as the Unreported
status is cleared by the alert reporting task and other block alert may
be reported without clearing the Active status, if the subcode has
changed.
The summary alarm is used for all process alarms in the block. The
cause of the alert is entered in the subcode field. The first alert to
become active sets the Active status in the Status parameter. As
soon as the Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing the Active
status, if the subcode has changed.
Used to set auto acknowledgment of alarms.
The amount the alarm value must return to within the alarm limit
before the associated active alarm condition clears.
The priority of the HI HI Alarm.
The setting for the alarm limit used to detect the HI HI alarm
condition.
The priority of the HI alarm.
The setting for the alarm limit used to detect the HI alarm condition.
The priority of the LO alarm.
The setting for the alarm limit used to detect the LO alarm condition.
The priority of the LO LO alarm.
The setting for the alarm limit used to detect the LO LO alarm
condition.
The priority of the deviation high alarm.
The setting for the alarm limit used to detect the deviation high alarm
condition.
The priority of the deviation low alarm.
The setting for the alarm limit use to detect the deviation low alarm
condition.
FOUNDATION Fieldbus Option User's Manual
Description
Page 83