Non-Critical Status 1 - Honeywell SLG 700 Option Manual

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Non-Critical Status 1

Non-Critical Status 1
High Sensor Electronics
Temperature
Surface in BDH
Surface in BDL
Sensor Not Characterization
Sensor Not Calibration
Field Background Not
Compatible
Background Not Set
Field Background Load Error
Rev.5
Possible Cause
The temperature of the sensor
housing is too high. Accuracy
and lifespan may decrease if
the temperature remains high.
This indicates that either the
surface or interface reflection
has been tracked into the
upper zone near the
Reference Plane where
measurements are not
accurate.
This indicates that either the
surface or interface reflection
has been tracked into the
lower zone near the End of
Probe where measurements
are not accurate.
Indicates the final sensor
characterization is incomplete.
Indicates the final sensor
calibration is incomplete.
The Field Background was
taken with a different set of
mounting configuration than
the current configuration.
The Field Background is
enabled before capture.
The Field Background could
not be loaded from non-volatile
memory.
FOUNDATION Fieldbus Option User's Manual
Recommended Action
Verify the environment temperature is
within specification. Take steps to
insulate the sensor housing from the
temperature source.
This is a condition that can occur
during normal operation and does not
generally require corrective action. If
this condition is triggered when it is
not expected, verify that the Blocking
Distance High parameter is set
correctly for the current conditions.
If distance to product is in Higher
zone then status associated with
device variables derived from
distance to product will be shown as
uncertain in local display and on host
the status would be poor accuracy.
This is a condition that can occur
during normal operation and does not
generally require corrective action. If
this condition is triggered when it is
not expected, verify that the Blocking
Distance Low parameter is set
correctly for the current conditions.
If distance to product is in Lower zone
then status associated with device
variables derived from distance to
product will be shown as uncertain in
local display and on host the status
would be poor accuracy.
The device is still available for use.
There may be an impact on the
accuracy of measurement.
The device is still available for use.
There may be an impact on the
accuracy of measurement.
Capture a new Field Background and
perform a soft or hard reset.
Capture a new Field Background and
perform a soft or hard reset.
Capture a new Field Background and
perform a soft or hard reset.
Page 59

Advertisement

Table of Contents
loading

Table of Contents