Parameter
BKCAL_IN_2
BAL_TIME
HYSTVAL
UPDATE_EVT
BLOCK_ALM

Attributes

Supported Modes
Alarm Types
Status Handling

3.16 Configuring the transmitter using Field Device Manager system

The transmitter can be configured through Field Device Manager (FDM), by using DTM for releases
R410 and R430 and using DD as well as DTM for release R440 and R450. For more information, refer
the FDM manuals #EP-FDM-11410, #EP-FDM-11430 and #EP-FDM-11440 for the corresponding
releases.
Rev.5
The analog input value and status from another block's
BKCAL_OUT output that is used for backward output
tracking for bump less transfer and to pass limit status.
The specified time for the internal working value of bias to
return to the operator set bias. Also used to specify the
time constant at which the integral term moves to obtain
balance when the output is limited and the mode is AUTO,
CAS, or RCAS.
Specifies the Hysteresis value.
This alert is generated by any change to the static data.
The BLOCK_ALM is used for configuration, hardware, and
connection failure or system problems in the block. The
cause of the alert is entered in the subcode field. The first
alert to become active sets the Active status in the Status
attribute. When the Unreported status is cleared by the
alert reporting task, another block alert is reported without
clearing the Active status, if the subcode has changed.
The block supports the following modes:
AUTO (Automatic)
IMAN (Manual)
OOS (Out of Service)
Cas
Standard block alarm
Sub-status values received at CAS_IN shall be passed to both
outputs, except for those used in the cascade handshake. An IFS
shall go to both outputs. The status option IFS if Bad CAS_IN is
available.
The splitter block shall propagate the BKCAL_IN status of Bad,
Device failure or Good Cascade, Fault State Active or Local
Override only if the statuses of both BKCAL_IN's contain a
propagated fault status.
FOUNDATION Fieldbus Option User's Manual