Parameter List

Table 11: Diagnostic Transducer block parameters
Parameter
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
BLOCK_ERR
UPDATE_EVT
BLOCK_ALM
EL_TEMP_DIAGNOSTIC
SENSOR_DIAGNOSTICS
POWER_TRAC
OP_VOLTAGE
TIME_IN_SERVICE
SERVICE_LIFE
STRESS_MONITOR
SENSOR_DETAILED_STATUS
SURFACE_SIGNAL_STRENGTH
INTERFACE_SIGNAL_STRENGTH
SURFACE_SIGNAL_QUALITY
INTERFACE_SIGNAL_QUALITY
HON_RES_1
HON_RES_2
HOS_RES_3
Page 62
FOUNDATION Fieldbus Option User's Manual
The revision level of the static data associated with the function
block.
The user description of the application of the block.
Used to identify grouping of blocks.
The identification number of the plant unit.
The actual, target, permitted, and normal modes of the block.
Reflects the error status associated with the hardware or
software components associated with a block. It is a bit string,
so that multiple errors may be shown.
This alert is generated by any change to the static data.
The BLOCK_ALM is used for all configuration, hardware, and
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active sets the Active status in the Status attribute. As
soon as the Unreported status is cleared by the alert reporting
task, another block alert may be reported without clearing the
Active status, if the subcode has changed.
Electronic Temperature Diagnostic parameters.
Sensor Diagnostics parameters.
Power Up Track Data.
Operating Voltage.
Summation of time in minutes that power has been applied to
the device since leaving the factory.
Elapsed Service life of device in percentage.
It monitors various diagnostic parameters which are then input
into an algorithm to calculate an estimated percent of time that
the transmitter has spent in stressful conditions.
Three Bytes whose constituent bits represent the various status
conditions set by the Sensor.
Displays Surface signal strength value and Status
Displays Interface Signal Strength Value and Status
Displays Interface Signal Strength Value and Status
Displays Interface Signal Strength Value and Status
Reserved for Honeywell use only.
Reserved for Honeywell use only.
Reserved for Honeywell use only
Description
Rev.5