Figure 17: Input Selector Schematic Diagram - Honeywell SLG 700 Option Manual

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

If SELECT_TYPE is Minimum, it transfers the lowest value to the output of the block. The
value of SELECTED is the number of the input with the lowest value.
If SELECT_TYPE is Maximum, it transfers the highest value to the output of the block.
The value of SELECTED is the number of the input with the highest value.
If SELECT_TYPE is Middle, if there are 3 or 4 values, the highest and lowest value is
discarded. The average of the remaining two values is computed, and the value is transferred
to the output of the block. The value of SELECTED becomes zero if an average is used,
else the value of SELECTED is the number of the input with the middle value.
If SELECT_TYPE is Average, it computes the average of the remaining inputs and
transfers the value to the output of the block. The value of SELECTED is the number of
inputs used in the average.
Rev.5

Figure 17: Input Selector Schematic Diagram

FOUNDATION Fieldbus Option User's Manual
Page 87