Honeywell SLG 700 Option Manual page 40

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Parameter
FD_VER
FD_RECOMMEN_ACT
FD_FAIL_PRI
FD_FAIL_MAP
FD_FAIL_MASK
FD_FAIL_ACTIVE
FD_FAIL_ALM
FD_MAINT_PRI
FD_MAINT_MAP
FD_MAINT_MASK
FD_MAINT_ACTIVE
FD_MAINT_ALM
FD_OFFSPEC_PRI
FD_OFFSPEC_MAP
FD_OFFSPEC_MASK
FD_OFFSPEC_ACTIVE
FD_OFFSPEC_ALM
FD_CHECK_PRI
FD_CHECK_MAP
Page 24
FOUNDATION Fieldbus Option User's Manual
A parameter equal to the value of the major version of the Field
Diagnostics specification that the device is designed for.
Enumerated list of recommended actions displayed with a device
alert.
Designates the alarming priority of the FAIL_ALM. The valid range is
0-15.
Mapped FAIL_ALM alarm conditions, and corresponds bit for bit to the
FAIL_ACTIVE. A bit on means that the corresponding alarm condition
is Mapped and it is detected. A bit off means the corresponding alarm
condition is disabled and is not detected.
Mask of FAIL_ALM. It corresponds to the bit of bit to FAIL_ACTIVE. A
bit on means that the condition is masked out from alarming.
Enumerated list of failure conditions within a device.
Alarm indicating a failure within a device which makes the device non-
operational.
Designates the alarming priority of the MAINT_ALM. The valid range
is 0-15.
Mapped MAINT_ALM alarm conditions and corresponds bit for bit to
the MAINT_ACTIVE. A bit on means that the corresponding alarm
condition is Mapped and is not detected. A bit off means the
corresponding alarm condition is disabled and is not detected.
Mask of MAINT_ALM. It corresponds to the bit of bit to
MAINT_ACTIVE. A bit on means that the condition is masked out
from alarming.
Enumerated list of maintenance conditions within a device.
Alarm indicating the device needs maintenance soon. If the condition
is ignored, the device eventually fails.
Designates the alarming priority of the OFFSPEC_ALM. The valid
range is 0-15.
Mapped OFFSPEC_ALM alarm conditions. Corresponds bit for bit to
the OFFSPEC_ACTIVE. A bit on implies that the corresponding alarm
condition is Mapped and detected. A bit off means the corresponding
alarm condition is disabled and is not detected.
Mask of OFFSPEC_ALM. It corresponds to the bit of bit to
OFFSPEC_ACTIVE. A bit on implies that the condition is masked out
from alarming.
Enumerated list of offspec conditions within a device.
Alarm indicating offspec alarms. These conditions do not have a direct
impact on the process or device integrity.
Designates the alarming priority of the CHECK_ALM. The valid range
is 0-15.
Mapped CHECK_ALM alarm conditions. Corresponds bit for bit to the
CHECK_ACTIVE. A bit on means that the corresponding alarm
condition is Mapped and is detected. A bit off means the
corresponding alarm condition is disabled and is not detected.
Description
Rev.5

Advertisement

Table of Contents
loading

Table of Contents