Parameter
UPDATE_EVT
BLOCK_ALM

Attributes

Supported Modes
Alarm Types
Status Handling
Rev.5
This alert is generated by any change to the static data.
The block alarm is used for all configuration, hardware, connection failure,
or system problems in the block. The cause of the alert is entered in the
subcode field. The first alert to become active sets the Active status in the
Status parameter. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported without clearing
the Active status, if the subcode has changed.
The block supports the following modes:
AUTO (Automatic)
MAN (Manual)
OOS (Out of Service).
The block supports standard block alarms, (see section 3.2).
During normal operations, the value and status of the selected input is
shown by OUT. If the number of inputs with Good status is fewer than
MIN_GOOD, then the output status is Bad.
The SELECTED output status is Good (NC), until the block is out of
service.
The block supports two status option:
Uncertain as Good: If the selected input status is Uncertain, set the
OUT status as Good.
Uncertain, if in Manual mode: If the block is set to Manual mode,
the status of the Output is set to Uncertain.
FOUNDATION Fieldbus Option User's Manual
Description
Page 89