6.4 to Install and launch the DTM

1. Install the softwares described in section 7.3.
2. Connect the Transmitter to the FF power conditioner.
3. Connect the NI modem at FF link terminal on power conditioner board.
4. Connect other end of NI modem USB connector to the PC COM port.
5. Run PACTware and select the Device Catalog option under the View menu. The Device
Catalog window should open to the right-hand side of the display.
6. Click on the Update Device Catalog button at the bottom of the Device Catalog window and
click on Yes in the confirmation pop-up window.
7. Select the Project option on the Window menu to close the Device Catalog window and select
the top level of the project view, which may be labeled HOST PC.
Rev.5
FOUNDATION Fieldbus Option User's Manual
Page 121