Parameter List; Table 18: Arithmetic Block Parameters - Honeywell SLG 700 Option Manual

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

9. Simple HTG compensated level, where PV is the tank base pressure, IN_1 is the top pressure, IN_2
is the density correction pressure, and GAIN is the height of the density tap.
10. Fourth order polynomial based on PV
�������� = PV + GAIN_IN_1×(����)
After the value of func is calculated, it is multiplied by GAIN, and then BIAS is added to the result.
Then, the high and low output limits are applied as per configured range scaling, and PRE_OUT is
updated with the calculated value. If the mode is AUTO, PRE_OUT is copied to OUT.

Parameter List

Parameter
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
BLOCK_ERR
PV
OUT
PRE_OUT
PV_SCALE
OUT_RANGE
GRANT_DENY
Page 102
(���� − (��_1))
�������� =
(���� − (��_2))
2
+ GAIN_IN_2×(����)
Table 19: Arithmetic block parameters
The revision level of the static data associated with the function block.
The revision value increments each time a static parameter value in the
block is changed.
The user description of the application of the block.
Used to identify grouping of blocks. This data is not checked of
processed by the block.
The identification number of the plant unit. This information may be used
in the host for sorting alarms, etc.
The actual, target, permitted, ad normal modes of the block.
Target: The mode to "go to"
Actual: The mode the "block is currently in"
Permitted: Allowed modes that target may take
Normal: Most common mode for target.
This parameter reflects the error status associated with the hardware or
software components associated with a block. It is a bit string so that
multiple errors may be shown.
It calculates the proportions of IN and IN_LO to for PV.
The analog output value and status.
Displays what would be the OUT value if the mode is AUTO or lower.
The high and low scale values, the engineering units' code, and the
number of digits to the right of the decimal point associated with the PV.
The high and low scale values, engineering units code, and number of
digits to the tight of the decimal point associated with OUT.
Options for controlling access of host computers and local control panels
to operating, tuning, and alarm parameters of the block. (Not used by
the device)
FOUNDATION Fieldbus Option User's Manual
3
+ GAIN_IN_3×(����)
Description
4
Rev.5