3.10.2.
Table 15 lists the valid ranges for the tuning parameters for the PID block. Note that OUT_LAG
parameter is not configurable when Ideal PID is selected (PID_FORM = 1) and can be configured
when Robust PID is selected (PID_FORM = 2).
The values given for these tuning parameters are valid under the following conditions:
The values assume that the minimum configurable PID function block execution period (T
is 0.125 seconds.
Algorithm typesetting (A, B, or C) has no effect on the validation of these tuning
parameters.
The PID function block rejects all values outside the following ranges:
Parameter
Initial
Value
PV_FTIME
0
GAIN
0
GAIN_NLIN
0
RATE
0
(sec.)
RESET
+INF
(sec.)
OUT_LAG
Ideal PID
N/A
Robust PID
0
BAL_TIME
0
Rev.5
PID Tuning Parameters
Table 15: PID Tuning parameters
Minimum
Maximum
Value
Value
0
200
.004
250
.004
250
32 • T
7500
s
2 • T
7500
s
N/A
N/A
2 • T
7500
s
N/A
N/A
FOUNDATION Fieldbus Option User's Manual
Comment
Units: seconds.
The value of ZERO is permitted to turn off rate action.
The value of +INF is permitted to turn off reset action.
(Some versions of NI configurator program cannot set
+/- INF).
Fixed for Ideal PID form - not configurable.
Zero permitted which implies no output lag.
Not used in Honeywell Implementation.
)
s
Page 79