Sensor Detailed Status; Critical Status 1; Table 9: Sensor Detailed Status - Honeywell SLG 700 Option Manual

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Sensor Detailed Status

SENSOR_DETAILED_STATUS parameter indicates the various status bits set by the sensor.
Table 10
shows the various possible bits that could be set.

Critical Status 1

Critical Status 1
Sensor Internal RAM Fault
External RAM Fault
Flash CRC Fault
Sensor Power Supply 2.5 OSC
Fault
Sensor Power Supply 2.5V
Fault
Sensor Power Supply 3.3V
Fault
Power Accumulator Fault
Rev.5
Table 10: Sensor Detailed Status
Possible Cause
RAM corruption detected.
RAM corruption detected.
The firmware has been
corrupted.
Power Accumulator
malfunction.
Power Accumulator
malfunction.
Power Accumulator
malfunction.
Power Accumulator
malfunction.
FOUNDATION Fieldbus Option User's Manual
Recommended Action
Power-cycle and see if the condition
re-occurs. If so, replacement of the
Sensor housing is required.
Power-cycle and see if the condition
re-occurs. If so, replacement of the
Sensor housing is required.
Attempt to reload the firmware. If the
problem persists, replacement of the
sensor housing will be required.
Power-cycle the device and if problem
persists replace Sensor housing If
problem still persists replace the
terminal block assembly.
Power-cycle the device and if problem
persists replace Sensor housing. If
problem still persists replace the
terminal block assembly.
Power-cycle the device and if problem
persists replace Sensor housing. If
problem still persists replace the
terminal block assembly.
Power-cycle the device and if problem
persists replace sensing housing... If
problem still persists replace the
terminal block assembly.