5.1 Installation

Be thoroughly familiar with the following contents before using the units to eliminate the causes which
occur the failure or malfunction of each unit.
5.1.1 Installation Environment and Space
Operating environment (Use the unit within the range of the general specifications when installing)
*Ambient temperatures:0 ~ +55 ℃
*Ambient humidity: 10% to 95% RH (at 25°C, non-condensing)
*Keep the height below 2000m.
*For use in pollution Degree 2 environment.
*Do not use it in the following environments.
Direct sunlight
-
Sudden temperature changes causing condensation.
-
Inflammable or corrosive gas.
-
Excessive airborne dust, metal particles or saline matter.
-
Benzine, paint thinner, alcohol or other organic solvents or strong alkaline solutions such as ammonia
-
or caustic soda.
Direct vibration, shock or direct drop of water.
-
Influence from power transmission lines, high voltage equipment, power cables, power equipment,
-
radio transmitters, or any other equipment that would generate high switching surges.
(Min.100mm or less)
Static electricity
-Before touching the unit, always touch a grounded piece of metal in order to discharge static electricity.
-In dry locations, excessive static electricity can cause problems.
Measures regarding heat discharge
• Always install the unit orientated with the tool port facing outward on the bottom in order to prevent the
generation of heat.
• Do not install the FP-X control unit as shown below.
• Do not install the unit above devices which generate heat such heaters, transformers or large scale
resistors.