Panasonic AFPX-C30R User Manual page 187

Fp-x series
Hide thumbs Also See for AFPX-C30R:
Table of Contents

Advertisement

For PC(PLC) link 1
Link relay allocation
System registers
No.
50
Range of link relays used
52
Starting No. of word for link relay transmission
53
Link relay transmission size
Note) No. 50 (range of link relays used) must be set to the same range for all the units.
Link register allocation
System registers
No.
51
Range of link registers used
54
Starting No. for link register transmission
55
Link register transmission size
Note) No. 51 (range of link registers used) must be set to the same range for all the units.
When link areas are allocated as shown above, the No. 1 send area can be sent to the No. 2, No. 3 and
No. 4 receive areas. Also, the No. 1 receive area can receive data from the No. 2 and No. 3 send areas.
No. 4 is allocated as a receive area only, and can receive data from No. 1, No. 2 and No. 3, but cannot
transmit it to other stations.
Note:
The PC link 1 can be used to connect with the second PC link W0 of the FP2 Multi Communication Unit
(MCU). At that time, the link relay number and link register number for the PC link can be the same
values as the FP2 (from WL64, from LD128).
Reference:
For the information on FP2-MCU, <Chapter 5 Communication Function PC(PLC) Link in FP2 Multi
Communication Unit Technical Manual ARCT1F396E>.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Name
Setting for various units
No. 1
No. 2
No. 3
64
64
64
64
84
104
20
20
24
Setting for various units
No. 1
No. 2
No. 3
128
128
128
128
128
208
40
40
48
No. 4
64
64
0
No. 4
128
128
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents