Supported commands
Executable
instructions for
master
F146 (RECV)
F146 (RECV)
F146 (RECV)
F146 (RECV)
F145 (SEND)
F145 (SEND)
Cannot be issued
F145 (SEND)
F145 (SEND)
Cannot be issued
Cannot be issued
Table for MODBUS reference No. and FP-X device No.
MODBUS reference No.
Coil
Input
Holding register
Input register
Note) For C14; MODBUS reference No.
FP-X device No.
Setting using FPWIN GR
1. Change the display to the "Online monitor" by selecting "Online Edit Mode" under "Online" in the menu
bar or pressing [CTRL] and [F2] keys at the same time.
2. Select "Options" in the menu bar, and then select "PLC Configuration". Click "COM Port". There are
separate tabs for setting the COM1 and COM2.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Code
Name (MODBUS
(decimal)
original)
01
Read Coil Status
02
Read Input Status
03
Read Holding Registers
04
Read Input Registers
05
Force Single Coil
06
Preset Single Register
08
Diagnostics
15
Force Multiple Coils
16
Preset Multiple Registers
22
Mask Write 4X Register
23
Read/Write 4X Registers
000001-001760
002049-006144
100001-101760
Note)
400001-432765
300001-300128
302001-302256
DT0-DT12784.
Name for FP-X
Read Y and R Coils
Read X Input
Read DT
Read WL and LD
Write Single Y and R
Write DT 1 Word
Loopback Test
Write Multiple Ys
and Rs
Write DT Multiple
Words
Write DT Mask
Read/Write DT
Data on BUS (hexadecimal)
0000-06DF
0800-17FF
0000-06DF
0000-7FFC
0000-007F
07D0-08CF
400001-411285, data on BUS (hexadecimal)
Remarks
(Reference No.)
0X
1X
4X
3X
0X
4X
0X
4X
4X
4X
FP-X device No.
Y0-Y109F
R0-R255F
X0-X109F
DT0-DT32764
WL0-WL127
LD0-LD255
0000-2FFC,