17.2 Table of Basic Instructions

Name
Boolean
Sequence basic instructions
Start
ST
Start Not
ST/
Out
OT
Not
/
AND
AN
AND Not
AN/
OR
OR
OR Not
OR/
Leading
edge
ST↑
start
Trailing
edge
ST↓
start
Leading
edge
AN↑
AND
Trailing
edge
AN↓
AND
Leading
edge OR
OR↑
Trailing
edge OR
OR↓
Leading
edge out
OT↑
Trailing
edge out
OT↓
Alterna-
ALT
tive out
AND
ANS
stack
OR stack
ORS
: Available,
: Not available,
*1) The type of the devices that can be specified depends on the models.
*2) This instruction is available for FP-X Ver. 2.0 or later, and FPΣ Ver. 3.10 or later.
*3) In the FP2/FP2SH/10SH, when using X1280, Y1280, R1120 (special internal relay included), L1280, T256, C256 or
anything beyond for the ST, ST/, OT, AN, AN/, OR and OR/ instructions, the number of steps is shown in parentheses.
Also, in the FP2/FP2SH/FP10SH, when a relay number has an index modifier, the number of steps is shown in
parentheses. For the FPΣ and FP-X, the number of steps varies according to the relay number to be used.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Symbol
Begins a logic operation with a Form A
(normally open) contact.
Begins a logic operation with a Form B
(normally closed) contact.
Outputs the operated result to the specified
output.
Inverts the operated result up to this
instruction.
Connects a Form A (normally open) contact
serially.
Connects a Form B (normally closed) contact
serially.
Connects a Form A (normally open) contact
in parallel.
Connects a Form B (normally closed) contact
in parallel.
Begins a logic operation only for one scan
when the leading edge of the trigger is
detected.
Begins a logic operation only for one scan
when the trailing edge of the trigger is
detected.
Connects a Form A (normally open) contact
serially only for one scan when the leading
edge of the trigger is detected.
Connects a Form A (normally open) contact
serially only for one scan when the trailing
edge of the trigger is detected.
Connects a Form A (normally open) contact
in parallel only for one scan when the leading
edge of the trigger is detected.
Connects a Form A (normally open) contact
in parallel only for one scan when the trailing
edge of the trigger is detected.
Outputs the operated result to the specified
output only for one scan when leading edge
of the trigger is detected. (for pulse relay)
Outputs the operated result to the specified
output only for one scan when trailing edge of
the trigger is detected. (for pulse relay)
Inverts the output condition (on/off) each time
the leading edge of the trigger is detected.
Connects the multiple instruction blocks
serially.
Connects the multiple instruction blocks in
parallel.
: Not available partially
Description
1
(2)
1
(2)
1
(2)
1
1
(2)
1
(2)
1
(2)
1
(2)
2
*2
*2
2
*2
*2
2
*2
*2
2
*2
*2
2
*2
*2
2
*2
*2
2
2
3
1
1