0 V to 10 V output
Conversion characteristics graph
Table of D/A converted values
Digital input value
0
400
800
1200
1600
2000
2400
2800
3200
3600
4000
When exceeding the rated range
Digital input value
Negative value
4001 or more
Each channel data is allocated as I/O data as shown below.
Analog output cassette
Output channel
CH0
Note:
• Use double-core twisted-pair shielded wires. It is recommended to ground them. However, depending
on the conditions of the external noise, it may be better not to ground the shielding.
• Do not have the analog output wiring close to AC wires, power wires, or load.
DA part Internal block diagram
A voltage amplifier and a current amplifier is connected in parallel to one DA converter IC.
Do not connect an analog device to the voltage output terminal and current output terminal of the same
channel simultaneously.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Output voltage (V)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
Analog output value
Unchanged
(Value preceding the input of a negative value)
Unchanged
(Value preceding the input of 4001)
Cassette mounting part 1
(Slot 0)
WY10
Installed slot No.
Cassette mounting part 2
(Slot 1)
WY20