Figure 3-7 3 Phase Power Connections (FP2AxxS & FP4AxxT only)
L1
Note 1
* Circuit
Breaker
Note 2
L1
For CE Compliance, refer to Section 8 of this manual.
A shared supply configuration is shown in Figure 3-8. The first drive must have an
internal power supply such as an Option "S" control.
MN1276
L2
L3
Earth
Note 3 & 4
L2
L3
PE
Baldor
Control
Figure 3-8 Shared Supply Power Connections
VCC+
VCC-
R1
R2
Baldor
Option S
Control
Regen
Resistor
Alternate *
Fuse
Connection
*
Components not provided with Control.
Notes:
1.
See Protection Device description in this section.
2.
Metal conduit or shielded cable should be used.
conduits so the use of a Reactor or RC Device does not interrupt
EMI/RFI shielding.
3.
Use the same gauge wire for Earth as used for L1, L2, L3
connections.
3.
Use same gauge wire for Earth ground as is used for L and N.
(VDE (Germany) requires 10mm
compliance, connect "PE" to the backplane of the enclosure.
4.
Reference EMC wiring in Section 8.
VCC+
VCC-
VCC+
VCC-
Baldor
Option P
Control
To
L1
L2
L3
Note 1
A1
B1
C1
2
minimum). For CE
VCC+
VCC-
VCC+
VCC-
Baldor
Option P
Control
Receiving & Installation 3-7