Figure 19. Ground Wiring

Note: Do not wire motor leads to R+, R–. This will cause damage to the drive.
Note: Actual layout may vary slightly by frame.
Ground Wiring
Run motor cables in separate conduit
DO NOT RUN CONTROL WIRES in same conduit
Cables sized per Appendix B
Provide dedicated wire for low impedance ground
between drive and motor. DO NOT USE conduit as ground
Improper grounding could result in damage to the motor and/
or drive and could void warranty.
CAUTION
Chapter 6—Installation Requirements
Control Wiring
7 .
Wire the control terminals following the details for the
specific option boards shown on the following pages.
Note: For ease of access, the board terminals blocks can be
unplugged for wiring.
8.
Wire control to the control board.
Note: Drive default is programmed for external interlock.
DG1 Series VFD MN040002EN—March 2014 www.eaton.com
33