For 230V Drive Series, required line and motor wire torque,
type and size range are listed in Table 42

Table 42. Required Line and Motor Wire Torque (230V)

Catalog
Number
Terminal Type
FR1
DG1-323D7xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
DG1-324D8xx-xxxx
DG1-326D6xx-xxxx
DG1-327D8xx-xxxx
DG1-32011xx-xxxx
FR2
DG1-32012xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
DG1-32017xx-xxxx
DG1-32025xx-xxxx
FR3
DG1-32031xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
DG1-32048xx-xxxx
FR4
DG1-32061xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
DG1-32075xx-xxxx
DG1-32088xx-xxxx
FR5
DG1-32114xx-xxxx
L1, L2, L3, DC+, DC–,
R+, R–, U, V, W
DG1-32143xx-xxxx
DG1-32170xx-xxxx
All Frames Sizes (FR1–FR5)
All models
Control terminal
block
Note
1
The line and motor wire size for DG1-32088xx-xxxx can only be 1/0 AWG.
Required
Required
Torque
Wire
(in-lb)
Range
12.1
14–10 AWG
12.1
14–10 AWG
12.1
14–10 AWG
12.1
14–10 AWG
12.1
12–10 AWG
15.6
10–6 AWG
15.6
8–6 AWG
15.6
8–6 AWG
40
6–2 AWG
40
4–2 AWG
95
3–1/0 AWG
95
2–1/0 AWG
95
1/0 AWG
1
354
3/0 AWG–
350 kcmil
354
4/0 AWG–
350 kcmil
354
300–350 kcmil
4.5
28~12 (Sol) AWG
30~12 (Str) AWG
DG1 Series VFD MN040002EN—March 2014 www.eaton.com
Appendix D—Safety Instructions for UL and cUL
Grounding
For 400V Drive Series, required grounding wire torque,
type and size range are listed in Table 43

Table 43. Required Line and Motor Wire Torque (400V)

Catalog
Number
Terminal Type
FR1
DG1-342D2xx-xxxx
Grounding terminal
DG1-343D3xx-xxxx
DG1-344D3xx-xxxx
DG1-345D6xx-xxxx
DG1-347D6xx-xxxx
DG1-349D0xx-xxxx
FR2
DG1-34012xx-xxxx
Grounding terminal
DG1-34016xx-xxxx
DG1-34023xx-xxxx
FR3
DG1-34031xx-xxxx
Grounding terminal
DG1-34038xx-xxxx
DG1-34046xx-xxxx
FR4
DG1-34061xx-xxxx
Grounding terminal
DG1-34072xx-xxxx
DG1-34087xx-xxxx
FR5
DG1-34105xx-xxxx
Grounding terminal
DG1-34140xx-xxxx
DG1-34170xx-xxxx
Required
Required
Torque
Wire
(in-lb)
Range
10
14–10 AWG
10
14–10 AWG
10
14–10 AWG
10
14–10 AWG
10
14–10 AWG
10
14–10 AWG
10
12–6 AWG
10
10–6 AWG
10
10–6 AWG
10
10–4 AWG
10
10–4 AWG
10
8–4 AWG
14
8–1/0 AWG
14
6–1/0 AWG
14
6–1/0 AWG
35
6 AWG–
250 kcmil
35
6 AWG–
250 kcmil
35
4 AWG–
250 kcmil
67