Table 44. Required Line And Motor Wire Torque (230V) - Eaton PowerXL DG1-323D7FB-C21C Installation Manual

Powerxl dg1 series vfd
Hide thumbs Also See for PowerXL DG1-323D7FB-C21C:
Table of Contents

Advertisement

Appendix D—Safety Instructions for UL and cUL
For 230V Drive Series, required grounding wire torque,
type and size range are listed as below:

Table 44. Required Line and Motor Wire Torque (230V)

Catalog
Number
Terminal Type
FR1
DG1-323D7xx-xxxx
Grounding terminal
DG1-324D8xx-xxxx
DG1-326D6xx-xxxx
DG1-327D8xx-xxxx
DG1-32011xx-xxxx
FR2
DG1-32012xx-xxxx
Grounding terminal
DG1-32017xx-xxxx
DG1-32025xx-xxxx
FR3
DG1-32031xx-xxxx
Grounding terminal
DG1-32048xx-xxxx
FR4
DG1-32061xx-xxxx
Grounding terminal
DG1-32075xx-xxxx
DG1-32088xx-xxxx
FR5
DG1-32114xx-xxxx
Grounding terminal
DG1-32143xx-xxxx
DG1-32170xx-xxxx
68
DG1 Series VFD MN040002EN—March 2014 www.eaton.com
Required
Required
Torque
Wire
(in-lb)
Range
10
14–10 AWG
10
14–10 AWG
10
14–10 AWG
10
14–10 AWG
10
14–10 AWG
10
12–6 AWG
10
10–6 AWG
10
10–6 AWG
10
10–4 AWG
10
10–4 AWG
14
8–1/0 AWG
14
6–1/0 AWG
14
6–1/0 AWG
35
6 AWG–
250 kcmil
35
6 AWG–
250 kcmil
35
4 AWG–
250 kcmil

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerxl dg1-324d8fb-c21cPowerxl dg1-326d6fb-c21cPowerxl dg1-32017fb-c21cPowerxl dg1-32012fb-c21cPowerxl dg1-32025fb-c21cPowerxl dg1-32048fb-c21c ... Show all

Table of Contents