PowerXL DG1 Series VFD
Improper drive operation:
If the drive is not turned on for a long period, the
●
performance of its electrolytic capacitors will be reduced.
If it is stopped for a prolonged period, turn the drive on at
●
least every six months for at least 5 hours to restore the
performance of the capacitors, and then check its
operation. It is recommended that the drive is not
connected directly to the line voltage. The voltage should
be increased gradually using an adjustable AC source.
Failure to follow these instructions can result in injury
and/or equipment damage.
For more technical information, contact the factory or your
local Eaton sales representative.