See Page 30 for cable stripping guidelines.
Table 29. North America Cable and Fuse Sizes—208 Vac to 240 Vac Ratings
208V Input
Frame
Amp
Current
Size
Suffix
(CT/I
)
H
FR1
3D7
3.2
4D8
4.4
6D6
6.1
7D8
7.2
011
10.2
FR2
012
10.2
017
16.2
025
23.1
FR3
031
28.7
048
44.4
FR4
061
56.4
075
69.4
088
81.4
FR5
114
105.5
143
132.3
170
157.3
FR6
211
195.2
261
241.4
Notes
1
Line and motor cable size is selected according to UL508C Table 40.3 for copper conductor rated 75°C. Use only with copper wire rated 75°C here.
Size requirements for other different wire types are defined in the National Electrical Code, ANSI/NFPA 70.
2
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL508C Table 6.4.
3
If power cubes or bypass are used, a UL recognized Class T fuse is recommended.
4
Available in 2015.
46
DG1 Series VFD MN040002EN—March 2014 www.eaton.com
NEC
NEC
208V Input
Motor Amp
Motor Amp
Current
Rating
Rating
(VT/I
)
at 230V
at 208V
L
4.4
4.2
4.6
6.1
6.0
6.6
7.2
6.8
7.5
10.2
9.6
10.6
11.6
16.3
15.2
16.7
23.2
22
24.2
29
28
30.8
44.2
42
46.2
56
54
59.4
64.6
68
74.8
78
80
88
94.3
104
114
129
130
143
157
154
169
189
192
211
248
261
4
312
312
4
Current
Current
Fuse
(CT/I
)
(VT/I
)
Rating
H
L
at 50°C
at 40°C
(Class T)
3.7
4.8
10
4.8
6.6
10
6.6
7.8
10
7.8
11
15
11
12.5
15
12.5
17.5
20
17.5
25
30
25
31
35
31
48
60
48
61
80
61
75
100
75
88
110
88
114
125
114
143
175
143
170
200
170
211
250
211
261
4
261
312
4
Terminal
NEC
Connection Size
Wire Size (AWG)
(AWG)
Line and
Line and
Motor
Ground
Motor
14
14
24–10
14
14
24–10
14
14
24–10
14
14
24–10
12
14
24–10
10
12
20–6
8
10
20–6
8
10
20–6
6
10
6–2
4
8
6–2
3
8
6–1/0
2
6
6–1/0
1/0
6
6–1/0
3/0
6
1/0–350
kcmil
4/0
6
1/0–350
kcmil
300
4
1/0–350
kcmil
3
4
4
3
4
4
Ground
18–10
18–10
18–10
18–10
18–10
12–6
12–6
12–6
14–4
14–4
10–1/0
10–1/0
10–1/0
8–250
kcmil
8–250
kcmil
8–250
kcmil
4
4

Hide quick links: