Eaton PowerXL DG1-323D7FB-C21C Installation Manual page 45

Powerxl dg1 series vfd
Hide thumbs Also See for PowerXL DG1-323D7FB-C21C:
Table of Contents

Advertisement

Power Wiring Notice
Do not discard the plastic bag containing the wiring
hardware.
1.
Remove the A-cover by removing (4) screws, then lifting
the A-cover away from the base.
Wiring Hardware Contents
European rubber grommet and flat rubber grommet
(for IP54 integrity)
Modification label
Detachable cable clamp
Attachable grounding strap
Ground strap mounting screws
Chapter 6—Installation Requirements
Power Wiring/Grounding
2.
Remove power wiring protection plate. Use power/
motor cable tables on Appendix B.
3.
Add attachable grounding clamps (qty 2), one on each
side of drive.
4.
Pass motor, input power wires/cables through base
wiring plate.
5.
If shielded cable is used, connect the shields of input
power and motor cables shields to ground.
6.
Wire power terminals (L1, L2, L3), motor terminal
(U, V, W), and grounding terminals per Figure 19. Power
and motor leads must be in separate conduit.
To meet the UL requirements, if conduit is being used
for wiring, the enclosure openings provided for conduit
connections in the field shall be closed by UL listed
conduit fittings with the same type rating (Type 1/
Type 12) as the enclosure.
DG1 Series VFD MN040002EN—March 2014 www.eaton.com