Table 31. North America Cable And Fuse Sizes-440 Vac To 500 Vac Ratings - Eaton PowerXL DG1-323D7FB-C21C Installation Manual

Powerxl dg1 series vfd
Hide thumbs Also See for PowerXL DG1-323D7FB-C21C:
Table of Contents

Advertisement

Appendix B—Installation Guidelines
Table 31. North America Cable and Fuse Sizes—440 Vac to 500 Vac Ratings
400V Input
Frame
Amp
Current
Size
Suffix
(CT/I
)
H
FR1
2D2
2.0
3D3
3.1
4D3
4.0
5D6
5.2
7D6
7.1
9D0
8.4
FR2
012
11.2
016
14.9
023
21.4
FR3
031
28.8
038
35.3
046
42.8
FR4
061
56.7
072
66.9
087
80.9
FR5
105
97.6
140
130.1
170
158.0
FR6
205
190.6
261
4
Notes
1
Line and motor cable size is selected according to UL508C Table 40.3 for copper conductor rated 75°C. Use only with copper wire rated 75°C here.
Size requirements for other different wire types are defined in the National Electrical Code, ANSI/NFPA 70.
2
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL508C Table 6.4.
3
If power cubes or bypass are used, a UL recognized Class T fuse is recommended.
4
Available in 2015.
48
DG1 Series VFD MN040002EN—March 2014 www.eaton.com
400V Input
NEC Motor
Current
Current
Amp Rating
(CT/I
(VT/I
)
at 460V
at 50°C
L
3.1
3.0
2.1
4
3.4
3.0
5.2
4.8
3.4
7.1
7.6
4.8
8.4
7.6
11.2
11
9
15
14
11
21.5
21
14
29
27
21
35.2
34
27
42.6
40
34
55.7
52
40
65.7
65
52
79.4
77
65
97
96
77
129
124
96
157
156
124
189
180
156
240
180
4
302
240
4
Current
Fuse
)
(VT/I
)
Rating
H
L
at 40°C
(Class T)
3.0
10
3.4
10
4.8
10
7.6
10
9
15
12
15
14
20
21
30
27
35
34
50
40
60
52
80
65
100
77
110
96
125
124
175
156
200
180
250
240
350
302
400
NEC
Terminal Connection
Wire Size (AWG)
Size (AWG)
Line and
Line and
Motor
Ground
Motor
14
14
30–10
14
14
30–10
14
14
30–10
14
14
30–10
14
14
30–10
14
14
30-10
12
12
20–6
10
10
20–6
8
10
20–6
8
10
6–2
6
10
6–2
4
8
6–2
4
8
6–1/0
3
6
6–1/0
1
6
6–1/0
3/0
6
1/0–350 kcmil
3/0
6
1/0–350 kcmil
250 kcmil
4
1/0–350 kcmil
3
4
4
3
4
4
Ground
18–10
18–10
18–10
18–10
18–10
18–10
12–6
12–6
12–6
14–4
14–4
14–4
10–1/0
10–1/0
10–1/0
8–250 kcmil
8–250 kcmil
8–250 kcmil
4
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerxl dg1-324d8fb-c21cPowerxl dg1-326d6fb-c21cPowerxl dg1-32017fb-c21cPowerxl dg1-32012fb-c21cPowerxl dg1-32025fb-c21cPowerxl dg1-32048fb-c21c ... Show all

Table of Contents