Table 32. International Cable And Fuse Sizes-380 Vac To 440 Vac Ratings - Eaton PowerXL DG1-323D7FB-C21C Installation Manual

Powerxl dg1 series vfd
Hide thumbs Also See for PowerXL DG1-323D7FB-C21C:
Table of Contents

Advertisement

Table 32. International Cable and Fuse Sizes—380 Vac to 440 Vac Ratings
400V Input
Frame
Amp
Current
Size
Suffix
(CT/I
)
H
FR1
2D2
2.0
3D3
3.1
4D3
4.0
5D6
5.2
7D6
7.1
9D0
8.4
FR2
012
11.2
016
14.9
023
21.4
FR3
031
28.8
038
35.3
046
42.8
FR4
061
56.7
072
66.9
087
80.9
FR5
105
97.6
140
130.1
170
158.0
FR6
205
190.6
261
4
Notes
1
Line and motor cable size is selected according to IEC60364–5–52:2009 Table B.52.4 for copper conductor with PVC insulation with a wiring condition of ambient
temperature 30°C in air and an installation method of "B2" (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the
standard of IEC60364–5–52:2009 for suitable cable sizes.
2
Earthing conductor size is determined by the cross–sectional area of phase conductors according to IEC/EN61800–5–1:2007 Table 5. So if phase conductor size
is changed, earthing conductor size should also be changed accordingly.
3
If power cubes or bypass are used, a Class gG/gL fuse is recommended.
4
Available in 2015.
400V Input
Current
Current
Current
(CT/I
)
(VT/I
H
(VT/I
)
at 50°C
at 40°C
L
3.1
2.2
3.3
4
3.3
4.3
5.2
4.3
5.6
7.1
5.6
7.6
8.4
7.6
9
11.2
9
12
15
12
16
21.5
16
23
29
23
31
35.2
31
38
42.6
38
46
55.7
46
61
65.7
61
72
79.4
72
87
97
87
105
129
105
140
157
140
170
189
170
205
205
261
4
261
310
4
Fuse
)
Rating
Mains and Motor
L
(gG/gL)
Cable Cu (mm
6
3*1.5+1.5
6
3*1.5+1.5
10
3*1.5+1.5
16
3*1.5+1.5
16
3*1.5+1.5
16
3*1.5+1.5
20
3*4+4
25
3*4+4
32
3*6+6
40
3*16+16
50
3*16+16
63
3*16+16
80
3*25+16
100
3*35+16
125
3*50+25
160
3*70+35
200
3*95+50
250
3*120+70
315
3*240+120
350
2*(3*95+50)
DG1 Series VFD MN040002EN—March 2014 www.eaton.com
Appendix B—Installation Guidelines
Terminal Cable Size
Main Terminal
2
2
)
Cu (mm
)
0.2–6 solid or
0.2–4 stranded
0.5–16
0.5–16
0.5–16
16–35
16–35
16–35
16–50
16–50
16–50
50–185
50–185
50–185
4
4
Earth Terminal
2
Cu (mm
)
0.75–6
0.75–6
0.75–6
0.75–6
0.75–6
0.75–6
4–16
4–16
4–16
2.5–25
2.5–25
2.5–25
6–50
6–50
6–50
10–120
10–120
10–120
4
4
49