Power Wiring Selection

Motor cable connections are made to terminals U, V, and W.

Cable Selection: Power and Motor Leads

Use UL approved heat-resistant copper cables only
75°C or higher for all units rated
Line voltage/mains should be Class 1 wire only outside
North America
Refer to the following tables for cable sizing guidelines
North America 208V to 240V: Appendix B
North America 380V to 500V: Appendix B
All other International 380V to 600V: Appendix B

Line (Mains) and Motor Cable Installation

The input line and motor cables must be sized in accordance
with the rated DG1 VFD input and output current.
If motor temperature sensing is used for overload protection,
the output cable size may be selected based on the motor
specifications.
Maximum symmetrical supply current is 100,000A RMS for
all size DG1 VFDs.
Input Fusing
Fuses are rated based on DG1 rated input and output
current. Use Class T (UL and cUL/CSA
60269-1). Refer to Appendix B for proper fuse size selection.
Consult with Eaton Electrical for further information on fusing
requirements.
®
) or type gG/gL (IEC
DG1 Series VFD MN040002EN—March 2014 www.eaton.com
Chapter 6—Installation Requirements

Connection Tightening Torque

Table 19. Tightening Torque

Frame
Power Wire
Size
In-Lb (Nm)
FR1
230V: 12.1 (1.4)
480V/575V: 5.5 (0.6)
FR2
15.6 (1.8)
FR3
40 (4.5)
FR4
95 (10.7)
FR5
354 (40)
FR6
Available in 2015
Notes
1
Strip the motor and power cables as shown in Figure 18 on next page.
2
Both UL and IEC tools may be used.
3
Applies to strained wire, solid wire, or ferrule installations.

Table 20. Spacing Between Parallel Motor Cables

Cable Length
Less than 164 ft (50m)
Less than 657 ft (200m)

Table 21. Maximum Motor Cable Length by Frame Size

without dV/dT Protected C2 Ratings

Frame Size
FR1
FR2
FR3
FR4
FR5
Notes
1
C1 protection requires external filtering. Consult factory.
b
C3 protection is covered under C2 protection levels.
1 2
Ground Wire
Control Wire
In-Lb (Nm)
In-Lb (Nm)
10 (1.1)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
10 (1.1)
4.5 (0.5)
14 (1.6)
4.5 (0.5)
35 (4.0)
4.5 (0.5)
Distance Between Cables
1 ft (0.3 m)
3 ft (1.0 m)
1 2
Maximum Cable Length (m)
100
150
150
200
200
3
29