[F174(Sp0H)] Pulse Output (Selectable Data Table Control Operation)7-21 - Panasonic FP0H User Manual

Control unit positioning/pwm output/high-speed counter
Hide thumbs Also See for FP0H:
Table of Contents

Advertisement

7.2.4 [F174(SP0H)] Pulse Output (Selectable Data Table Control Operation)
Outputs pulses from a specified pulse output channel according to a specified data table.
 Instruction format
R0
DF
 Operand
Operand
Settings
S
Starting number of the area in which data tables are registered
n
Target channel for pulse output
 Memory area type that can be specified
Operand
WX
WY
S
-
n
-
 Outline of operation
• Outputs pulses from a specified channel according to the settings specified in the data table
starting with the address specified by [S] when a corresponding control active flag is OFF
and the execution condition is ON.
• Switches the pulse frequency when the elapsed value of the high-speed counter reaches the
target value set in the data table. (It is performed by the interrupt processing.)
• Stops the pulse output when the elapsed value reaches the final target value.
• For setting the frequency to 50 kHz or more, specify the duty of 1/4 (25%).
7.2 FP Compatible Instruction Mode Control Instruction
F174 SP0H
WR
WL
SV
-
-
-
-
-
-
-
-
S
n
EV
DT
LD
I
-
A
-
-
-
-
-
-
Constant
Index
modifier
K
H
-
-
A
A
A
-
7-21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents