6-2. How to Read Special Internal Relays(R) & Special Data Registers(DT)

3. Table of Special Data Registers(DT)

The special data registers are used for special purposes in the Programmable Controller.
Data cannot be transferred to the special data registers(except for DT9060 to DT9122).
DT9017/DT9018(Data Transfer instructions ; Error program address)
Address
Description
DT9017
The error program address is stored, when R9007 turns ON.
DT9018
The error program address is stored, when R9008 turns ON.
DT9039(Data Transfer instructions ; Error code)
Address
Description
DT9039
The following error code is stored, when R9031 turns ON.
71(hexadecimal) : Response signal meaning that a Data Transfer operation cannot be received.
72(hexadecimal) : The Data Transfer buffer is full.
73(hexadecimal) : Response message cannot be received.
When one of the above mentioned errors occurs, check the time-out value in the system register
number 32. The time out value can be set in the range of 10ms to 81.9s(default = 2s).
DT9140 to DT9159(P/W PC Link status)
Address
Description
DT9140
DT9141
P/W
PC Link 0 Multiply the value stored here by 2.5 ms.
DT9142
DT9143
DT9144
DT9145
DT9146
DT9147
DT9148
DT9149
P/W
PC Link 1 Multiply the value stored here by 2.5 ms.
DT9150
DT9151
DT9152
DT9153
DT9154
DT9155
DT9156
P/W
DT9157
PC Link 0 Work area for calculating the data sending interval
DT9158
P/W
DT9159
PC Link 1 Work area for calculating the data sending interval
76
Ring counter :
Counts how many times data is received from the other stations.
Current data reception interval :
Minimum data reception interval :
Multiply the value stored here ne 2.5 ms.
Maximum data reception interval :
Multiply the value stored here by 2.5 ms.
Ring counter :
Counts how many times data is sent to the other stations.
Current data sending interval :
Multiply the value stored here by 2.5 ms.
Minimum data sending interval :
Multiply the value stored here by 2.5 ms.
Maximum data sending interval :
Multiply the value stored here by 2.5 ms.
Ring counter :
Counts how many times data is received from the other stations.
Current data reception interval :
Minimum data reception interval :
Multiply the value stored here by 2.5 ms.
Maximum data reception interval :
Multiply the value stored here by 2.5 ms.
Ring counter :
Counts how many times data is sent to the other stations.
Current data sending interval :
Multiply the value stored here by 2.5 ms.
Minimum data sending interval :
Multiply the value stored here by 2.5 ms.
Maximum data sending interval :
Multiply the value stored here by 2.5 ms.
Work area for calculating the data reception interval
Work area for calculating the data reception interval