Network Configuration Settings - Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual

Melsec iq-r series cc-link ie field network
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

Network Configuration Settings

Set parameters of slave stations (the number of points and assignment of link devices) in the master station and submaster
station.
Setting procedure
The procedure for the network configuration settings is shown below.
1.
Select the module in "Module List" and drag it to the list of stations or the network map.
List of stations
Network map
2.
Set the required items.
3.
Select [Close with Reflecting the Setting] to finish the network configuration settings.
When changing the network configuration settings after setting "Safety Communication Setting" under
"Application Settings", correct the safety communication setting.
Setting items
Item
Description
[Detect Now] button
Automatically reads the information of slave stations.
For details, refer to the following.
 iQ Sensor Solution Reference Manual
Mode Setting
The mode of the master station is displayed.
Assignment Method
Select a link device assignment method.
• Point/Start: Enter the points and start numbers of link devices.
• Start/End: Enter the start and end numbers of link devices.
Link Scan Time
The approximate link scan time is displayed.
(Approx.)
No.
The total number of slave stations and submaster stations set in "Network Configuration
Settings" is displayed.
Model Name
The module model name is displayed.
To set a module where the profile is not registered, select it from the "General CC IE Field
Module" list or register the profile before setting the model name. For how to register a
profile, refer to the following.
 GX Works3 Operating Manual
STA#
Enter the station number of each slave station or the submaster station connected to the
network.
Station numbers do not need to be set consecutively, but must be unique.
The station number of the master station is fixed at "0".
Drag and drop the text.
Setting range
• Point/Start
• Start/End
(Default: Start/End)
1 to 120
(Default: Blank)
2 PARAMETER SETTINGS
2.3 Basic Settings
2
129

Hide quick links:

Advertisement

Table of Contents
loading