Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual page 277

Melsec iq-r series cc-link ie field network
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

Error
Error details and causes
code
D723H
System link start/stop was requested during link start/
stop processing.
D724H
Link startup/stop station specification is incorrect.
D725H
System link start/stop was requested from a local
station.
D726H
The request command of transient transmission is
incorrect.
D727H
Link start was requested from a station other than the
station which had requested link stop.
D728H
Data link startup instruction was executed to the
station which is performing data link.
D729H
Link stop of the own station was instructed in the
station with no station number setting.
D731H
Forced master switching command was executed from
a station other than the submaster station operating as
a master operating station.
D740H
Transient transmission failed.
D741H
A station type error of the execution station was
detected.
D742H
Transient transmission failed.
D743H
A station type error of the execution station was
detected.
D744H
Flash ROM clear failed.
D783H
A transient transmission error was detected.
D784H
A transient transmission error was detected.
Action
Retry the operation after the stop or restart of data link
is completed.
Check the setting, and stop or start data link.
A local station cannot start or stop data link of all or
multiple stations. Perform these operations from the
master station.
Correct the request command at the request station,
and retry the operation.
• Data link start was instructed from a station different
from the one that had instructed the data link stop.
Instruct data link start and data link stop from the
same station.
• The method of the data link start differs from that of
the data link stop. Instruct the data link start using
the same method as the data link stop. (Ex. Data
link is stopped using the CC-Link IE Field Network
diagnostics, and the data link is started using a
program.)
• Data link start has failed. Forcibly restart the data
link.
Execute the data link startup instruction to the station
where data link had been stopped.
Specify the station number using the UINI instruction,
and execute the instruction again.
Perform the forced master switch to the submaster
station operating as a master operating station.
• If a slave station is disconnected from the network,
identify the cause of the disconnection and take
action.
• When data link is stopped in the slave station,
identify the cause of the data link stop and take
action.
• Retry the operation after a slave station is replaced
and new one is added.
• Perform the operation after data link starts on the
master operating station.
• The operation cannot be performed in the local
station and submaster operating station. Perform
the operation in the master operating station.
After completion of the transient transmission, retry
the operation.
The operation cannot be performed on a local station.
Perform the operation in the master station and
submaster station.
• The flash ROM may be faulty. Check the wire and
cable distances and grounding condition of each
device, and take measures against noise.
• Execute the module communication test. If the error
occurs again even after taking the above, the
possible cause is a hardware failure of the module.
Please consult your local Mitsubishi representative.
• Close the CC-Link IE Field Network diagnostics
window in the engineering tool, and perform the
diagnostics again.
• Check the read request data at the request station,
and retry the operation.
• Close the CC-Link IE Field Network diagnostics
window in the engineering tool, and perform the
diagnostics again.
• Check the read request data at the request station,
and retry the operation.
Detailed Information
4 TROUBLESHOOTING
275
4.5 List of Error Codes
4