Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual page 181

Melsec iq-r series cc-link ie field network
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

12.
Set the network configuration as follows.
[Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Basic Settings]  [Network
Configuration Settings]
• RX/RY and RWw/RWr setting of the local station is for standard communications.
• RX/RY setting of the remote device station is used as a remote control and monitor input signal in standard
communications.
• RWw/RWr setting of the remote device station is used in the system of safety communications. Always set 16 points.
13.
Set the refresh settings as follows.
[Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Basic Settings]  [Refresh Settings]
• The refresh settings are for standard communications.
14.
Log on to the programmable controller.
[Online]  [User Authentication]  [Log on to PLC]
• If logon cannot be performed, writing user information or initializing all information of the programmable controller is
required. ( GX Works3 Operating Manual)
15.
Write the set parameters to the Safety CPU on the master station.
[Online]  [Write to PLC]
3.3 Communication Example of Safety Communication Function
3 PROGRAMMING
179