Error
Error details and causes
code
D244H
The transient data is incorrect.
D245H
The target station number of the dedicated instruction
is incorrect.
D246H
The transient data is incorrect.
D247H
When the dedicated instruction was executed,
response from the target station was received twice.
D249H
The target station's CPU type of the dedicated
instruction is incorrect.
D24AH
The arrival monitoring time of the dedicated instruction
is incorrect.
D24BH
The number of resends specified in the dedicated
instruction is incorrect.
D24CH
The network number specification of the dedicated
instruction is incorrect.
D24DH
The channel specified in the dedicated instruction is
incorrect.
4 TROUBLESHOOTING
266
4.5 List of Error Codes
Action
• Correct the transient data at the request source,
and retry the operation.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
• Execute again after correcting the target station
number at the request source.
• If the request source is on another network, check if
the routing parameters are set correctly, and take
action.
• Correct the transient data at the request source,
and retry the operation.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
• Check the network status using the CC-Link IE Field
Network diagnostics of the engineering tool, and
take action.
• Check if the switching hub and the cables at the
request source are connected properly.
• If the request source is on another network, check if
the routing parameters are set correctly, and take
action.
• Execute again after correcting the CPU type of the
target station at the request source.
• If the request source is on another network, check if
the routing parameters are set correctly, and take
action.
• Execute again after correcting the arrival monitoring
time at the request source.
• When the own station, target station, or relay station
detected an error, identify the cause of the error and
take action.
• Lower the transient transmission usage frequency,
and then perform again.
• When "Communication Mode" in "Application
Settings" of the master station (submaster station) is
set to "High-Speed", change it to "Normal" and retry
the operation.
• Check if the switching hub and the cables at the
request source are connected properly.
• Execute again after correcting the number of
resends at the request source.
• When the own station, target station, or relay station
detected an error, identify the cause of the error and
take action.
• Lower the transient transmission usage frequency,
and then perform again.
• When "Communication Mode" in "Application
Settings" of the master station (submaster station) is
set to "High-Speed", change it to "Normal" and retry
the operation.
• Check if the switching hub and the cables at the
request source are connected properly.
• Execute again after correcting the network number
at the request source.
• If the request source is on another network, check if
the routing parameters are set correctly, and take
action.
• Set 1 to 2 for the target channel number in the
control data when executing the SEND instruction.
• Set 1 to 32 for the channel number when executing
the REMFR/REMTO/REMFRD/REMTOD
instruction.
• Execute again after correcting the number of the
channel used by own station in the control data.