Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual page 329

Melsec iq-r series cc-link ie field network
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

No.
Name
SW0110
CPU minor error status
to
of each station
SW0117
SW0118
Redundant CPU system
to
status of each station
SW011F
Description
Stores the minor error or continuation error occurrence status of each station.
When the target station is the master/local module, the occurrence status on the
control CPU is stored.
0: Normal operation, or a moderate or serious error (stop error) occurring
1: Minor error (continuation error) occurring
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0110
16 15 14 13 12 11 10
SW0111
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW0112
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW0113
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW0114
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW0115
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW0116
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW0117
Each number in the table represents a station number.
 is fixed to 0.
(Conditions)
• This register is enabled when 'Baton pass status of own station' (SB0047) is off.
• When 'Baton pass status of own station' (SB0047) is turned on (error), data prior
to error is held.
• This register is enabled only for normally operating stations in 'Baton pass status
of each station' (SW00A0 to SW00A7).
• Reserved stations and stations higher than the maximum station number are
ignored.
Stores the redundant CPU system status (control/standby system) of each station
(including the own station).
0: Control system
1: Standby system
"0" is stored for a station other than a redundant system station.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0118
16 15 14 13 12 11 10
SW0119
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW011A
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW011B
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW011C
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW011D
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW011E
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW011F
(Conditions)
• This register is enabled when 'Baton pass status of own station' (SB0047) is off.
• When 'Baton pass status of own station' (SB0047) is turned on, data prior to error
is held.
• This register is enabled only for normally operating stations in 'Baton pass status
of each station' (SW00A0 to SW00A7).
• Reserved stations and stations higher than the maximum station number are
ignored.
9
8
7
6
5
4
3
2
1
120 119 118 117 116 115 114 113
9
8
7
6
5
4
3
2
1
120 119 118 117 116 115 114 113
Appendix 5 List of Link Special Register (SW)
Availability
Master
Local
station
station
(submaster
station)
APPX