Communications with different networks

This function performs the transient transmission seamlessly to stations on different networks using dedicated instructions
and the engineering tool.
Engineering tool
Ethernet
Network No.3
Communications can be made with stations up to eight networks apart (number of relay stations: 7). (
Page 335 Dedicated Instruction)
When the networks consist of only MELSEC iQ-R series
Communication paths are automatically set for communication with the following networks of MELSEC iQ-R series.
• Ethernet
• CC-Link IE Controller Network
• CC-Link IE Field Network
■Setting method
Check that "Dynamic Routing" in "Application Settings" is set to "Enable".
• Communication paths are automatically set, but they can also be manually set. ( Page 36 When the
networks consist of MELSEC iQ-R series and other series)
• Communication paths cannot be automatically set to Ethernet-equipped modules connected via a router.
Set communication paths manually for such modules. ( Page 36 When the networks consist of
MELSEC iQ-R series and other series)
When the networks consist of MELSEC iQ-R series and other series
Setting communication paths allows communication with the following networks configured with modules other than MELSEC
iQ-R series.
• Ethernet
• CC-Link IE Controller Network
• CC-Link IE Field Network
• MELSECNET/H
• MELSECNET/10
1 FUNCTIONS
36
1.2 Transient Transmission
CC-Link IE Controller Network
Network No.1
CC-Link IE Field Network
Network No.2
(Relay station)