RUGGEDCOM ROS
User Guide
4.
Click Apply.
Section 5.4.11
Configuring the MicroLok Protocol
To configure the MicroLok protocol for a serial port, do the following:
1.
Make sure the serial port is configured to use the MicroLok protocol. For more information, refer to
Section 5.4.5, "Configuring a Serial Port"
2.
Navigate to Serial Protocols » Configure Protocols » Configure MicroLok . The MicroLok form appears.
5
Figure 93: MicroLok Form
1. Transport List 2. IP Port Box 3. Link Stats Options 4. DSCP Box 5. Apply Button 6. Reload Button
3.
Configure the following parameter(s) as required:
Parameter
Transport
IP Port
Link Stats
DSCP
4.
Click Apply.
Configuring the MicroLok Protocol
.
Description
Synopsis: { TCP, UDP, Disabled }
Default: UDP
The network transport used to transport protocol data over an IP
network.
Synopsis: 1024 to 65535
Default: 60000
A local port number on which the MicroLok protocol listens for
UDP datagrams or TCP connections.
Synopsis: { Disabled, Enabled }
Default: Enabled
Enables link statistics collection for this protocol.
Synopsis: 0 to 63
Default: 0
To set the DS byte in the IP header. DS byte setting is supported in
the egress direction only.
Chapter 5
Setup and Configuration
1
2
3
4
6
153