Modbus Tcp Performance Determinants - Siemens RUGGEDCOM ROS User Manual

Hide thumbs Also See for RUGGEDCOM ROS:
Table of Contents

Advertisement

RUGGEDCOM ROS
User Guide
Protocol (TCP), respecting the Modbus TCP protocol, and forwards the frame to a Server Gateway or native
Modbus TCP RTU. Returning responses are stripped of their TCP headers and issued to the master.
The Modbus Server application accepts TCP encapsulated Modbus TCP messages from Client Gateways and native
masters. After removing the TCP headers, the messages are issued to the RTU. Responses are TCP encapsulated
and returned to the originator.
The following illustrates a complex network of Client Gateways, Server Gateways and native TCPModbus devices.
1
2
3
Figure 79: Modbus Client and Server
1. Master (Polling RTUs 1 and 2)    2. Master (Polling RTUs 1, 2 and 4)    3. Native Modbus TCP Master (Polling All RTUs)    4.  RMC30 Client
Gateway    5.  RUGGEDCOM Media Converter Client Gateway    6. Ethernet    7.  RUGGEDCOM Media Converter Server Gateway    8. 
RMC30 Server Gateway    9. RTU 1    10. RTU 2    11. RTU 3    12. RTU 4
Section 5.4.2.2

Modbus TCP Performance Determinants

The following illustrates the possible sources of delay and error in an end-to-end Modbus TCP exchange.
Modbus TCP Performance Determinants
4
5
1
Setup and Configuration
6
7
7
Chapter 5
8
9
10
11
133

Advertisement

Table of Contents
loading

Table of Contents