Chapter 5
Setup and Configuration
11
Figure 100: Telnet Com Port Form
1. Port Box    2. Pack Char Box    3. Pack Timer Box    4. Pack Size Box    5. Flow Control Options    6. Call Dir List    7. Loc Port Box   
8. Rem Port Box    9. IP Address Box    10. Link Stats Options    11. Apply Button    12. Reload Button
4.
Configure the following parameter(s) as required:
Parameter
Port
Pack Char
Pack Timer
Pack Size
Flow Control
Call Dir
160
Description
Synopsis:   1 to maximum port number
Default:   1
The serial port number as seen on the front plate silkscreen of the
RMC30.
Synopsis:   0 to 255 or { Off }
Default:   Off
The character that will be used to force the forwarding of
buffered data to the network. If a packetization character is not
configured, buffered data will be forwarded based upon the
packetization timeout (Pack Timer) parameter.
Synopsis:   1 to 1000
Default:   10 ms
The delay from the last received character until when data is
forwarded. If parameter value is set to be less than 3 ms, there is
not guaranty that it will be obeyed. It will be a minimum possible
time in which device can react under certain data load.
Synopsis:   16 to 1400 or { Maximum }
Default:   Maximum
The maximum number of bytes received from serial port to be
forwarded.
Synopsis:   { None, XON/XOFF }
Default:   None
The Flowcontrol setting for serial port.
Synopsis:   { In, Out, Both }
Configuring the Telnet Com Port Protocol
RUGGEDCOM ROS
User Guide
1
2
3
4
5
6
7
8
9
10
12