Broadcast Rtu Polling - Siemens RUGGEDCOM ROS User Manual

Hide thumbs Also See for RUGGEDCOM ROS:
Table of Contents

Advertisement

RUGGEDCOM ROS
User Guide
Figure 76: RTU Polling
1. Host    2. Host with Port Redirection Software    3.  RMC30     4. Ethernet    5. RTU
If a server is used at the host end, it will wait for a request from the host, encapsulate it in an IP Datagram and
send it to the remote side. There, the remote server will forward the original request to the RTU. When the RTU
replies, the server will forward the encapsulated reply back to the host end.
The server maintains configurable timers to help decide if replies and requests are complete.
The server also handles the process of line-turnaround when used with RS485. It is important to note that
unsolicited messages from RTUs in half-duplex mode cannot be supported reliably. Message processing time
includes sending a message over RS485, a packtimer and a turnaround time. To handle half-duplex mode reliably,
the turnaround time must be configured long enough to allow an expected response to be received. Any other
messages will not be sent to the RS485 line within the processing time. If such a message is received from the
network, it will be delayed. It is up to the application to handle polling times on ports properly.
Section 5.4.1.3

Broadcast RTU Polling

Broadcast polling allows a single host-connected server to distribute a polling stream to a number of remote
Remote Terminal Units (RTUs).
The host equipment connects via a serial port to a server. Up to 64 remote servers may connect to the host server
via the network.
Broadcast RTU Polling
1
3
2
4
3
4
3
Chapter 5
Setup and Configuration
5
5
129