Siemens RUGGEDCOM ROS User Manual page 170

Hide thumbs Also See for RUGGEDCOM ROS:
Table of Contents

Advertisement

Chapter 5
Setup and Configuration
11
Figure 96: DNP over RawSocket Form
1. Port Box    2. Response Time Box    3. Response Dest Options    4. Transport Options    5. Call Dir List    6. Max Conns Box    7. Loc
Port Box    8. Rem Port Box    9. IP Address Box    10. Link Stats Options    11. Apply Button    12. Reload Button
4.
Configure the following parameter(s) as required:
Parameter
Port
Response Time
Response Dest
Transport
Call Dir
156
Description
Synopsis:   1 to 4
Default:   1
The port number as seen on the front plate silkscreen on the
switch.
Synopsis:   50 to 60000 ms or { Off }
Default:   Off
The maximum allowable time to wait for the response on serial
port.
Synopsis:   All, Last requester
Default:   All
The destination where data received from serial port will be sent.
If the value of Response Time is not 'Off', Response Dest will be
autmatically set to All when record is applied.
Synopsis:   { TCP, UDP }
Default:   TCP
The network transport used to transport protocol data over the IP
network.
Synopsis:   { In, Out, Both }
Default:   In
The Call direction for TCP Tranport.
• In: accepts an incoming connection.
• Out: places an outgoing connection
• Both: places an outgoing connection and waits for as incoming
connection (both directions).