S5-115U Manual
4
PLC System Start-Up and Program Test
This chapter contains notes on starting up an S5-115U with information on testing your STEP 5
control program.
A prerequisite is knowledge of the principle of operation of the PLC (see Chapter 2).
There are notes on starting up a system at the end of the chapter.
4.1
Prerequisites for Starting Up a PLC
Make sure that
•
all necessary I/O modules are plugged into suitable slots (see Chapter 3)
•
the address assignment of the inputs and outputs is in order (see Chapter 6)
•
the control program to be tested is available on the programmer.
4.2
Steps for System Start-Up
4.2.1
Overall Reset
You are recommended to perform the Overall Reset function before entering a new program.
Overall Reset deletes the following:
•
PLC program memory
•
All data (flags, timers and counters)
•
All error IDs.
In addition, all system data is automatically assigned default values after Overall Reset so that the
system data area assumes a defined "basic status".
EWA 4NEB 811 6130-02b
PLC System Start-Up and Program Test
4-1