STEP 5 Operations
Processing Operation
Table 8-25 and the example that follows explain the processing operation.
Operation
Operand
DO =
Formal operands
1 As actual operands, function blocks cannot have block parameters
Example:
Function Block Call
STL
:JU FB 35
NAME
:PROCES
D5
:
DB 5
DW2
:
DW 2
D6
:
DB 6
DW1
:
DW 1
Q4
:
QW 4
MOT5
:
FB 36
:BE
8-64
Table 8-25. Processing Operation
Process formal operand
The substituted blocks are called unconditionally.
Actual Operands Permitted
1
DB, PB, SB, FB
Program in Function Block FB35
:DO
=D5
:L
=DW2
:DO
=D6
:T
=DW1
:T
=Q4
:DO
=MOT5
:BE
S5-115U Manual
Meaning
Parameter
Type
B
Executed Program
:
C
DB
:L
DW
:C
DB
:T
DW
:T
QW
:JU
FB
:BE
EWA 4NEB 811 6130-02b
Data
Type
5
2
6
1
4
36