Installation Guidelines
Possible Configurations on Mounting Rack ER 701-3
Use expansion mounting rack ER 701-3 to install expansion unit EU 3. EU 3 is suitable for con-
nection to a centrally configured or remote CC 2/CC 3 central controller. ER 701-3 has slots for a
power supply module (PS), digital and analog input or output modules, communications
processors and intelligent input/output modules (interrupt-triggering modules can only be used
via an IM 307/317), one central controller interface module, and one IM 306 expansion unit
interface module. The IM 306 lets you connect up to three EU 1 expansion units to one EU 3
expansion unit.
Use the IM 310, IM 311, IM 314 and 318 central controller interface modules to connect the EU 3
to the S5-135U, S5-150U and S5-155U programmable controllers.
Mounting Rack
ER 701-3
Slots
1
Power Supply Module
2
Digital Module
3
Analog Module
IM 306
IM 314/318
AS 310/311
IM 317
CP 513/523...526/
4
535/552
CP 530-7
4
4
CP
5430/CP
143-0AB01
IP 241 ... 245/260/261
4
IP
240/246/247/252
WF 625/725/470/480
3
ÜBW 313
DIMOS Interface module
Only with adapter casing
1 Use of the IP 246/247 and the CP 513/524/525/526/527/535/143 is not permissible with a 3 A power supply
module (the DSI signal is not generated by the power supply)
2 Except the 434-7 input module; digital modules of ES 902 design (S5-135/155U) can be plugged into slot 0 to 6
3 Not permissible with the AS 302/311; analog modules of ES 902 design (S5-135/155U) can be plugged into
slot 0 to 6
4 Only when IM 304 is connected to IM 314 and when IM 307 is connected to IM 317
Figure 3-12. Possible Configurations on Mounting Rack ER 701-3
3-12
PS
0
1
4
2
3
4
5
S5-115U Manual
6
7
IM
EWA 4NEB 811 6130-02b