Indirect Initialization of SSNR, A-NR and ANZW
Job Status Word as Flags
Parameter Assignments
C
DB 44
JU
FB 244
NAME :
SEND
SSNR :
KY 255,1
.
A-NR
:
KY 0,0
ANZW :
FW 0
DB
44
DW 1
KY 0,1
DW 2
KY 0,31
DW 3
KS MW
DW 4
KY 0,200
Job Status Word in a Data Block
Parameter Assignments
C
DB 24
JU
FB 244
NAME :
SEND
SSNR :
KY 255,1
.
.
A-NR
:
KY 0,0
ANZW :
FW 0
DB
24
DW 1
KY 0,1
DW 2
KY 0,31
DW 3
KS DB
DW 4
KY 222,10
DB
222
DW 10
DW 11
EWA 4NEB 811 6130-02b
Explanation
Open DB44
ID for indirect initialization
The data area for initialization begins with DW 1.
Irrelevant
Irrelevant
The interface number is 1.
The job number is 31.
The job status word is in the flag area.
The job status word is represented in flag words
FW 200 and FW 202.
Explanation
Open DB24
ID for indirect initialization
The data area for parameter assignment begins at
data word 1.
Irrelevant
Irrelevant
The interface number is 1.
The job number is 31.
The job status word is in a data block.
Address of the ANZW (DW 10 and DW 11 in DB222)
Job status word
Integral Blocks