Integral Blocks
DB30
STL
0:
KH = 0000;
1:
KF = +01000;
2:
KH = 0000;
3:
KF = +01000;
4:
KH = 0000;
5:
KF = +00010;
6:
KH = 0000;
7:
KF = +00010;
8:
KH = 0000;
9:
KF = +00000;
10:
KH = 0000;
11:
KM = 00000000 00100000;
12:
KF = +00500;
13:
KH = 0000;
14:
KF = +02000;
15:
KH = 0000;
16:
KF = -02000;
17:
KH = 0000;
18:
KH = 0000;
19:
KH = 0000;
20:
KH = 0000;
21:
KH = 0000;
22:
KF = +00000;
23:
KH = 0000;
24:
KF = +00000;
25:
KH = 0000;
26:
KH = 0000;
27:
KH = 0000;
28:
KH = 0000;
29:
KF = +00000;
30:
KH = 0000;
31:
KH = 0000;
32:
KH = 0000;
33:
KH = 0000;
34:
KH = 0000;
35:
KH = 0000;
36:
KH = 0000;
37:
KH = 0000;
38:
KH = 0000;
39:
KH = 0000;
40:
KH = 0000;
41:
KH = 0000;
42:
KH = 0000;
43:
KH = 0000;
44:
KH = 0000;
45:
KH = 0000;
46:
KH = 0000;
47:
KH = 0000;
48:
KF = +00000;
49:
KH = 0000;
50:
11-44
Description
K PARAMETER (HERE=1), FACTOR 0.001
(VALUE RANGE: -32768 TO 32767)
R PARAMETER (HERE=1), FACTOR 0.001
(VALUE RANGE: -32768 TO 32767)
TI=TA/TN(HERE=0.01), FACTOR 0.001
(VALUE RANGE: 0 TO 9999)
TD=TV/TA(HERE=10), FACTOR 1
(VALUE RANGE: 0 TO 999)
SETPOINT W, FACTOR 1
(VALUE RANGE: -2047 TO 2047)
CONTROL WORD
MANUAL VALUE YH, FACTOR 1
(VALUE RANGE: -2047 TO 2047)
UPPER CONT. LIMIT BGOG, FACTOR 1
(VALUE RANGE: -2047 TO 2047)
LOWER CONT. LIMIT BGUG, FACTOR 1
(VALUE RANGE: -2047 TO 2047)
ACTUAL VALUE X, FACTOR 1
(VALUE RANGE: -2047 TO 2047)
DISTURBANCE VARIABLE Z, FACTOR 1
(VALUE RANGE: -2047 TO 2047)
FEEDFORWARD XZ FOR DIFF.,
FACTOR 1 (-2047 TO 2047)
CONTROLLER OUTPUT Y, FACTOR 1
(VALUE RANGE: -2047 TO 2047)
S5-115U Manual