9.3

Process Interrupt Generation with the 434-7 Digital Input Module

The 434-7 digital input module is an interrupt module with programmable interrupt generation.
9.3.1

Function Description

The process interrupts are processed in two different ways:
Interrupt-initiating inputs can be identified by the control program.
A yellow LED lights up on the module and a relay contact is closed (the relay contact can be
accessed externally via the "MELD" outputs). This signal remains even in the event of power
failure and can be reset by applying 24 V to the 24 V RESET input.
Although the 434-7 digital input module has only eight inputs, it occupies two bytes in the input
I/O area and two bytes in the output I/O area, i.e. you can access two bytes of inputs and two
bytes of outputs (input byte and output byte each have the same address). Because the 434-7
digital input module occupies two I/O bytes, the IM 306 has to be set to 16 channels for this
module.
The addresses of the two consecutive I/O bytes occupied by the 434-7 are referred to in the follo-
wing as "module address" and "module address+1".
Use the two bytes of outputs in the restart OB for initializing the module (the "module
address" byte indicates which input triggers the interrupt and the "module address+1" byte
determines the type of the interrupt-initiating edge)
You must use the two bytes of inputs when
- you want to scan the status of the inputs (scan the "module address" byte)
- you want to indentify inputs which have triggered the interrupt (scan the "module
address+1" byte; only in interrupt program).
The status of the inputs must be scanned direct (L PY) since it is not transferred to the PII.
9.3.2

Start-Up

Assign a slot address to the module; the IM 306 interface module is to be set to 16 channels
for the 434-7 digital input module!
9.3.3

Initialization in Restart OBs

The following must be programmed in the RESTART blocks OB21 and OB22:
Which inputs are to trigger an interrupt
Whether the interrupt is to be triggered by a rising or falling edge.
This information is stored in two bytes which the program in OB21 or OB22 transfers to the
module.
In the "module address" byte, mark which inputs are to trigger an interrupt, and in the "module
address+1" byte, mark which edge is to trigger the interrupt.
EWA 4NEB 811 6130-02b
Interrupt Processing
9-5