Siemens SIMATIC S5-115U User Manual page 649

Simatic s5 series cpu 941-7ub11 cpu 942-7ub11 cpu 943-7ub11 and cpu 943-7ub21 cpu 944-7ub11 and cpu 944-7ub21
Table of Contents

Advertisement

S5-115U Manual
Electrostatic charging of objects and persons
Every object with no conductive connection to the electrical potential of its surroundings can be
charged electrostatically. In this way, voltages up to 15000 V can build up whereas minor charges,
i.e. up to 100 V, are not relevant.
Examples:
Plastic covers
Plastic cups
Plastic-bound books and notebooks
Desoldering device with plastic parts
Walking on plastic flooring
Sitting on a padded chair
Walking on a carpet (synthetic)
Limits for perceiving electrostatic discharges
An electrostatic discharge is
perceptible from 3500 V
audible from 4500 V
visible from 5000 V
A fraction of those voltages is capable of destroying or damaging electronic devices.
Carefully note and apply the protective measures described below to protect and prolong the life
of your modules and components.
General protective measures against electrostatic discharge damage
Keep plastics away from sensitive devices. Most plastic materials have a tendency to build up
electrostatic charges easily.
Make sure that the personnel, working surfaces and packaging are sufficiently grounded
when handling electrostatic sensitive devices.
If possible, avoid any contact with electrostatic sensitive devices. Hold modules without
touching the pins of components or printed conductors. In this way, the discharged energy
cannot affect the sensitive devices.
EWA 4NEB 811 6130-02b
Active and Passive Faults in Automation Equipment
up to 5000 V
up to 5000 V
up to 8000 V
up to 8000 V
up to 12000 V
up to 15000 V
up to 15000 V
D-3