S5-115U Manual
FB10 STL
NAME
:UHR-STEL
DECL
:LPYR
I/Q/D/B/T/C: I
DECL
:WDAY
I/Q/D/B/T/C: I
DECL
:DATE
I/Q/D/B/T/C: I
DECL
:MON
I/Q/D/B/T/C: I
DECL
:YEAR
I/Q/D/B/T/C: I
DECL
:HOUR
I/Q/D/B/T/C: I
DECL
:AMPM
I/Q/D/B/T/C: I
DECL
:MIN
I/Q/D/B/T/C: I
DECL
:SEC
I/Q/D/B/T/C: I
DECL
:ERR
I/Q/D/B/T/C: Q
DECL
:MODE
I/Q/D/B/T/C: I
:A
=MODE
:=
F
11.1
:AN
F
20.0
:JC
=M001
:R
F
20.0
:
:C
DB
2
:L
=LPYR
:T
DL
4
:L
=WDAY
:T
DR
4
:L
=DAY
:T
DL
5
:L
=MON
:T
DR
5
:L
=YEAR
:T
DL
6
:L
=HOUR
:ON
=AMPM
:ON
=MODE
:JC
=MORN
:L
KH 0080
:OW
MORN :T
DR
6
:L
=MIN
:T
DL
7
:L
=SEC
:T
DR
7
:AN
F
11.2
:S
F
11.2
:L
KT 020.1
:SV
T
10
M001 :A
T
10
:BEC
EWA 4NEB 811 6130-02b
SETTING THE CLOCK
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
BI/BY/W/D: BI
24-HR MODE = 0, 12-HR MODE = 1
(CLOCK MODE STATUS WORD BIT 1)
FLAG IS RESET IF SETTINGS ALREADY
READ INTO CLOCK DATA AREA
CLOCK DATA AREA
STORE VALUE FOR LEAP YEAR
STORE VALUE FOR WEEKDAY
STORE VALUE FOR DATE
STORE VALUE FOR MONTH
STORE VALUE FOR YEAR
STORE VALUE FOR HOUR
IF 12-HR MODE IS SET, AND
AMPM BIT = 1 (AFTERNOON), THE
RELEVANT BIT IN THE CLOCK AREA
IS SET
STORE VALUE FOR MINUTES
STORE VALUE FOR SECONDS
TRANSFER SETTINGS
(STATUS WORD IS FW10)
START MONITORING TIME
BEC, IF MONITORING TIME
NOT YET ELAPSED
Integral Real-Time Clock
Description
13-15