S5-115U Manual
3.2.5

Centralized Configurations

A central controller (CC 0, CC 1, CC 2 or CC 3) connected via short connecting cables to as many as
three expansion units makes up a centralized configuration. Use only the IM 305 or IM 306
interface modules to connect an ER 701-1 mounting rack.
For centralized configuration with the IM 305, please note the following points:
You can use fixed slot addressing only (see Chapter 5).
The 0.5 m (1.6 ft.) connecting cable is not long enough to connect the EU under the CC. Use an
IM 306 interface module or the IM 305 version with a longer cable for such an arrangement.
Table 3-2. Comparison of the IM 305 and IM 306 Interface Modules
Number of EUs (maximum)
Total cable length
Slot addressing
Current supplied to EUs (maximum)
* The EU with the most current supplied should be as close to the CC as possible.
CR 700-
0/1/2/3
ER 701-1
CR 700-
0/1/2/3
Power Supply Module
Central Processing Unit
IM 305 Interface Module
**
You can also order a 1.25 m (4.1 ft.) 705 connecting cable (Order No. 6ES5 705-0BB20) or a 2.5 m (6.7 ft.) 705 con-
necting cable (Order No. 6SE5 705-0BC50), and use them to mount two EUs next to each other.
Figure 3-19. Centralized Configuration with the IM 305 and IM 306 Interface Modules
EWA 4NEB 811 6130-02b
Configuration with IM 305
1
0.5 or 1.5 m (1.6 or 4.8 ft.)
fixed (for CC and EU)
1 A
ER 701-1
ER 701-1 Mounting Rack
IM 306 Interface Module
705 Connecting cable **
Installation Guidelines
Configuration with IM 306
3
maximum 2.5 m (8.2 ft.)
variable (for CC and EU)
2 A
*
ER 701-1
ER 701-1
ER 701-1
CR 700-
0/1/2/3
3-19