S5-115U Manual
9.4.3
Operating the Module without Alarm Processing
You can also use the module as a straightforward digital input/output module, in which case, the
mode selector on the back of the module is set to the "ALARM OFF" position. When operating
without alarm processing, you can use the module in all central controllers (CR 700-0/1/2/3) and in
all expansion units (ER 701-0/1/2/3). Further parameterizing of the module is not required. You
can address the module like any normal input/output module without restriction.
Address assignments when operating the module without alarm processing
•
4 input bytes are assigned in the process I/O image from the base address.
7
x
7
x +1
7
x+2
7
x +3
•
4 output bytes are assigned in the process I/O from the base address.
7
x
7
x +1
7
x+2
7
x +3
Figure 9-5. Address Assignment when Operating "Without Alarm Processing"
EWA 4NEB 811 6130-02b
0
0
3 input bytes for
24 input channels
0
0
The input byte (x + 3) can be
read but the contents are not
significant
0
2 output bytes for
16 output channels
0
0
These output bytes can be
written to but this has no
effect on the outputs.
0
Interrupt Processing
Process I/O image
Process I/O image
9-17