Siemens SIMATIC S5-115U User Manual page 483

Simatic s5 series cpu 941-7ub11 cpu 942-7ub11 cpu 943-7ub11 and cpu 943-7ub21 cpu 944-7ub11 and cpu 944-7ub21
Table of Contents

Advertisement

S5-115U Manual
Transmitting Data
The length of the frame to be transmitted (in bytes) must be entered in the first word of the
Send mailbox.
Send mailbox
Frame length
Data
The data to be transmitted must be entered in the remaining words of the Send mailbox.
Set bit 7 in the CBS (a rising edge triggers the transmission). The driver resets this bit when
transmission has been completed.
If data transmission is not possible, bits 0 to 6 of the CBS contain an error code describing the error
in more detail. Table 12-19 provides information on the meanings of the various error codes.
Bit 7
Send permitted:
A rising edge
initiates trans-
mission
EWA 4NEB 811 6130-02b
Word 1
Word 2
Word n
Figure 12-19. Structure of the Send Mailbox
Coordination Byte for Send (CBS)
Error code (see Table 12-19)
Figure 12-20. Structure of the CBS
Communications Capabilities
Bit 1
Bit 0
12-49